Menu
Your Cart
image of Leoch 65AH UPS Battery with Spec and Price in BDT

Leoch 65AH UPS Battery

Key Features of Leoch 65AH :
Brand: Leoch
Rated Voltage: 12V
Nominal Capacity: 65Ah
Short-circuit current: 1495A
Internal Resistance: Approx 7 mΩ (Fully charged)


CALL FOR DETAILS: 01958510719, 01969633055

Leoch 65AH UPS Battery
৳27,500.00
Specification:
Key Features
attr - Key Feature 1 > Brand: Leoch
attr -Key Feature 2 > Rated Voltage: 12V
attr -Key Feature 3 > Nominal Capacity: 65Ah
attr -Key Feature 4 > Short-circuit current: 1495A
attr -Key Feature 5 > Internal Resistance: Approx 7 mΩ (Fully charged)
Call Info >


CALL FOR DETAILS: 01958510719, 01969633055

Leoch Battery
Rated Voltage 12V
Nominal Capacity Nominal Capacity (25℃):
C10,1.80V/cell: 65Ah
Dimension Length: 348mm (13.7inches)
Width: 167mm (6.57inches)
Container Height:178mm (7.01inches)
Total Height: 178mm (7.01inches)
Approx Weight 19.2kg (42.3lbs)
Terminal T6(M6)
Container Material ABS (UL94 HB or V-0 optional)
Short-circuit current 1495A
Internal Resistance Approx 7 mΩ (Fully charged)
Operating Temp. Range Discharge: -15~50℃ (5~122°F)
Charge: -20~40℃ (-4~104°F)
Storage: -15~40℃ (5~104°F)
Nominal Operating Temp. Range 25±3℃ (77±5°F)
Max.Charging Current Max.Charging Current (25℃): 0.3C
Charge voltage Standby Use: 2.25-2.30V/cell
Cycle Use: 2.35-2.40V/cell
Temp. Coeffcient -3mV/cell/℃
-5mV/cell/℃
Effect of temp. to Capacity 40℃ (104°F): 103%
25℃ (77°F): 100%
0℃ (32°F): 86%
Self Discharge ≤3% per month at 25°C (77°F).
LP series batteries may be stored up to 6 months at 25°C (77°F) and then a freshening charge is required.
For higher temperatures the time interval will be shorter.